Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 6, 2016, 05:33 AM
  • 22 0690_22 0689A_20160505_234942.mp4

Date
05/05/2016
W/O
568953
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00827
PipeID
P17044
Time
10:33 PM
Certificate
U- 109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K 3203
Sewer Name
22 SUNFLOWER TRUNK
City
LA VERNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
15
Purpose
Routine Assessment
Project
WO_568953_TV22063_MAY2016
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
12 in.
Upstream MH
22 0690
Downstream MH
22 0689A
Dir. of Survey
Downstream
Length Surveyed
302 ft.
Total Length
302 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
108
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
110
Pipe schematic from manhole 22 0690 to 22 0689A
MH: 22 0690MH: 22 0689Adownstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 06900 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. VC - Vermin Cockroach2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"52.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"57.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"127.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"132.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"206.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"211.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"281.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"286 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"299.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish301.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK301.9 ft. VC - Vermin Cockroach302 ft. AMH - Downstream Manhole, Survey Ends - 22 0689A

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
211.6TFA
9.9TB
127.2TF
2SAV
301.9MGOCONNECTION AT THE MH 3 O'CLOCK
0MWL
0AMH22 0690
299.6SAV
301.9VC
57.6TF
52.7TFC
132.2TFC
302AMH22 0689A
0MWM
281.4TFC
286TFA
0VC
206.7TFC

Properties (4)

additional_info
SC300651
custom_field_two
3
customer
LACSD
datetime
2016-05-05T22:33:55-07:00