Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2016, 07:23 AM
  • 22 0699_ 22 0698_20160505_023015.mp4

Date
05/05/2016
W/O
568953
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00827
PipeID
P17053
Time
12:23 AM
Certificate
U- 109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K 3202
Sewer Name
22 SUNFLOWER TRUNK
City
LA VERNE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
15
Purpose
Routine Assessment
Project
WO_568953_TV22063_MAY2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
22 0698
Downstream MH
22 0699
Dir. of Survey
Upstream
Length Surveyed
200.3 ft.
Total Length
200.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
512G
O&M Rating
85
Overall Index
2
Overall Quick
Overall Rating
85
Pipe schematic from manhole 22 0698 to 22 0699
MH: 22 0698MH: 22 0699upstream0 ft. OBZ - Obstacles Other, 85 %of cross sectional area, from 02 to 11 o'clock - DEBRIS0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0 ft. MSA - Survey Abandoned - AND MATCH FOOTAGE40 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"108.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"181.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"198.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start200.3 ft. MWM - Water Mark, 30 %of cross sectional area200.3 ft. AMH - Downstream Manhole, Survey Ends - 22 0698200.3 ft. MWL - Water Level, 10 %of cross sectional area200.3 ft. MGO - Reversal Inspection200.3 ft. MGO - General Observation - CONNECTION AT THE MH 9 O' CLOCK

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Obstacles Other, 85 %of cross sectional area, from 02 to 11 o'clock - DEBRIS

    200.3 ft. - Obstacles Other, 85 %of cross sectional area, from 02 to 11 o'clock - DEBRIS

  • Survey Abandoned - AND MATCH FOOTAGE

    200.3 ft. - Survey Abandoned - AND MATCH FOOTAGE

Observations (12)

DistanceCodeObservation
2DAGS
0MWM
160.3TF
200.3OBZDEBRIS
0AMH22 0698
200.3DAGS
0MWL
0MGO
200.3MSAAND MATCH FOOTAGE
0MGOCONNECTION AT THE MH 9 O' CLOCK
19.1TF
92TFC

Properties (4)

additional_info
SC226250
custom_field_two
4
customer
LACSD
datetime
2016-05-05T00:23:29-07:00