Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 9, 2016, 07:23 PM
  • 22 0664_22 0663A_20160509_132854.mp4

Date
05/09/2016
W/O
568953
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00827
PipeID
P17013
Time
12:23 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3247
Sewer Name
22 SUNFLOWER TRUNK
City
SAN DIMAS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
22
Purpose
Routine Assessment
Project
WO_568953_TV22063_MAY2016
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0664
Downstream MH
22 0663A
Dir. of Survey
Downstream
Length Surveyed
16.8 ft.
Total Length
16.8 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 22 0664 to 22 0663A
MH: 22 0664MH: 22 0663Adownstream0 ft. MGO - General Observation - Magnesium hydroxide coating start0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 22 06640 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start14 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish16.8 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK16.8 ft. AMH - Downstream Manhole, Survey Ends - 22 0663A

Observations (9)

DistanceCodeObservation
0MGOMagnesium hydroxide coating start
16.8MGOCONNECTION AT THE MH 9 O'CLOCK
16.8AMH22 0663A
0MGOCONNECTION AT THE MH 3 O'CLOCK
0AMH22 0664
2SAV
0MWL
14SAV
0MWM

Properties (4)

additional_info
SC305346
custom_field_two
3
customer
LACSD
datetime