- Date
- 01/01/2002
- W/O
- 568953
- Weather
- Dry
- Operator/Surveyor
- J. HARTOOG
- Sewer ID
- Z00827
- PipeID
- P17014
- Time
- 7:08 AM
- Certificate
- U-507-03-3386
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K3247
- Sewer Name
- 22 SUNFLOWER TRUNK
- City
- SAN DIMAS
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 22
- Page No.
- 22
- Purpose
- Routine Assessment
- Project
- WO_568953_TV22063_MAY2016
- Sewer Type
- GRAVITY
- Material
- NRCP
- Shape
- Circular
- Height
- 15 in.
- Upstream MH
- 22 0664
- Downstream MH
- 22 0665
- Dir. of Survey
- Upstream
- Length Surveyed
- 293.8 ft.
- Total Length
- 293.8 ft.
- Structural Index
- 3
- Structural Quick
- 3K00
- Structural Rating
- 174
- O&M Index
- 2
- O&M Quick
- 2J11
- O&M Rating
- 115
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 289
Pipe schematic from manhole 22 0664 to 22 0665 Observation photos (3)

7.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

60.5 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"

205 ft. - Roots Fine Connection, from 02 to 04 o'clock, within 8 inches of joint: NO