Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 23, 2016, 08:07 AM
  • 02 0585_02 0584 _09232016_010707.mp4

Date
09/23/2016
W/O
592159
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00258
PipeID
P03129
Time
1:07 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3716
Sewer Name
02 EAST COMPTON BOULEVARD EXTENSION TRUNK
City
BELLFLOWER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
WO_592159_TV02289_SEP2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0585
Downstream MH
02 0584
Dir. of Survey
Downstream
Length Surveyed
352.4 ft.
Total Length
352.4 ft.
Structural Index
2
Structural Quick
2111
Structural Rating
3
O&M Index
2
O&M Quick
2M00
O&M Rating
136
Overall Index
2
Overall Quick
Overall Rating
139
Pipe schematic from manhole 02 0585 to 02 0584
MH: 02 0585MH: 02 0584downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 05857.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start53.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"196.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES346.3 ft. CC - Crack Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES349.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish352.4 ft. AMH - Downstream Manhole, Survey Ends - 02 0584

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    7.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    196.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES

    346.3 ft. - Crack Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
352.4AMH02 0584
196.5CL
346.3CC
0MWM
7.4DAGS
53.5TFA
0MWL
349.6DAGS
0AMH02 0585

Properties (5)

additional_info
SC303702
custom_field_two
4
customer
LACSD
datetime
2016-09-23T01:07:00-07:00
lining
CIPP