Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 23, 2016, 09:47 AM
  • 02 0593_02 0592 _09232016_024623.mp4

Date
09/23/2016
W/O
592159
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00258
PipeID
P03137
Time
2:47 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3716
Sewer Name
02 EAST COMPTON BOULEVARD EXTENSION TRUNK
City
BELLFLOWER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
WO_592159_TV02289_SEP2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0593
Downstream MH
02 0592
Dir. of Survey
Downstream
Length Surveyed
315.5 ft.
Total Length
315.5 ft.
Structural Index
3
Structural Quick
3623
Structural Rating
24
O&M Index
2
O&M Quick
2K00
O&M Rating
124
Overall Index
2
Overall Quick
Overall Rating
148
Pipe schematic from manhole 02 0593 to 02 0592
MH: 02 0593MH: 02 0592downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 05932.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start53.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"57.5 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES139.3 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES192.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 4"194 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES214.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start222.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish291.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES294.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO, Start310.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO, Finish313.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish315.5 ft. AMH - Downstream Manhole, Survey Ends - 02 0592

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    57.5 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    139.3 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    194 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    214.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    291.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO, Start

    294.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO, Start

Observations (16)

DistanceCodeObservation
192.7TF
2.1DAGS
0MWM
194CS
0MWL
294.5FL
57.5CL
0AMH02 0593
139.3CM
310.6FL
315.5AMH02 0592
313.9DAGS
53.5TFA
222.5FL
291.1CL
214.7FL

Properties (4)

additional_info
SC303702
custom_field_two
4
customer
LACSD
datetime
2016-09-23T02:47:00-07:00