Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 23, 2016, 08:29 AM
  • 02 0583_02 0582 _09232016_012935.mp4

Date
09/23/2016
W/O
592159
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00258
PipeID
P03127
Time
1:29 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3716
Sewer Name
02 EAST COMPTON BOULEVARD EXTENSION TRUNK
City
BELLFLOWER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
WO_592159_TV02289_SEP2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0583
Downstream MH
02 0582
Dir. of Survey
Downstream
Length Surveyed
327 ft.
Total Length
327.1 ft.
Structural Index
3
Structural Quick
4131
Structural Rating
9
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
137
Pipe schematic from manhole 02 0583 to 02 0582
MH: 02 0583MH: 02 0582downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 05831.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start14.4 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES45.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"47 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES99 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 4"111.2 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES153.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"206 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"263.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 4"321.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"324.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish327.1 ft. AMH - Downstream Manhole, Survey Ends - 02 0582

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    1.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    14.4 ft. - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    47 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

    111.2 ft. - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
47FM
99TF
0MWL
263.9TF
0MWM
327.1AMH02 0582
1.6DAGS
324.1DAGS
14.4CM
45.9TFA
153.2TFA
206TFA
0AMH02 0583
111.2FC
321.9TFA

Properties (4)

additional_info
SC303702
custom_field_two
4
customer
LACSD
datetime
2016-09-23T01:29:00-07:00