Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 14, 2018, 07:25 AM
  • Section#1_02 2090_02 2089__4142018__G6985.mp4

Date
04/14/2018
W/O
0695755
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00247
PipeID
P04406
Time
12:25 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6985
Sewer Name
02 DOUGLAS AVENUE RELIEF TRUNK
City
East Los Angeles
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Capital Improvement Program Assesment
Project
04122018VMR_DOUGLAS_AVENUE_RELIEF_TRUK
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
02 2090
Downstream MH
02 2089
Dir. of Survey
Downstream
Length Surveyed
261.2 ft.
Total Length
261.2 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
7
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 02 2090 to 02 2089
MH: 02 2090MH: 02 2089downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:51 am0 ft. MWL - Water Level, 10 %of cross sectional area2.7 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES34 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4" - OPEN110.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - OPEN115.8 ft. MWLS - Water Level, Sag in pipe, 30 %of cross sectional area, Start128.2 ft. MWLS - Water Level, Sag in pipe, 30 %of cross sectional area, Finish176.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4" - OPEN261.2 ft. AMH - Downstream Manhole, Survey Begins - 01:21 am

Observations (10)

DistanceCodeObservation
0MWM
110.1TFOPEN
128.2MWLS
0AMH12:51 am
2.7CM
261.2AMH01:21 am
34TFOPEN
0MWL
176.1TFOPEN
115.8MWLS

Properties (4)

custom_field_two
3
customer
LACSD
datetime
2018-04-14T00:25:05-07:00
year_laid
19820504