Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 6, 2016, 07:45 AM
  • 15 0612A_15 0612_06042016_005543.mp4

Date
04/06/2016
W/O
563459
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00601
PipeID
P12548
Time
12:45 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3308
Sewer Name
15 DOUBLE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_563459_TV15205_APRIL2016
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
10 in.
Upstream MH
15 0612A
Downstream MH
15 0612
Dir. of Survey
Downstream
Length Surveyed
151.4 ft.
Total Length
151.4 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
90
O&M Index
2
O&M Quick
2E00
O&M Rating
60
Overall Index
3
Overall Quick
Overall Rating
150
Pipe schematic from manhole 15 0612A to 15 0612
MH: 15 0612AMH: 15 0612downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 0612A0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start43.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"82.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"128.1 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"134.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"150 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish150 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish151.4 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK151.4 ft. AMH - Downstream Manhole, Survey Ends - 15 0612

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0MWL
150SAP
2DAGS
151.4MGOACTIVE CONNECTION AT MH 3 O'CLOCK
150DAGS
128.1TBA
151.4AMH15 0612
0AMH15 0612A
82.8TFA
0MWM
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0MGOCOCKROACHES IN MANHOLE
2SAP
43.4TF
134.1TF

Properties (4)

additional_info
SC305435
custom_field_two
3
customer
LACSD
datetime
2016-04-06T00:45:41-07:00