Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 29, 2018, 10:01 AM
  • 15 0099_15 0098_29032018_031604.mp4

Date
03/29/2018
W/O
1590881
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00590
PipeID
P11977
Time
3:01 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5514
Sewer Name
15 ABBEY STREET TRUNK
City
LA PUENTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
38
Purpose
Routine Assessment
Project
WO_690161_TV15204_MAR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0099
Downstream MH
15 0098
Dir. of Survey
Downstream
Length Surveyed
285.2 ft.
Total Length
285.2 ft.
Structural Index
3
Structural Quick
4122
Structural Rating
8
O&M Index
1
O&M Quick
4131
O&M Rating
19
Overall Index
2
Overall Quick
Overall Rating
27
Pipe schematic from manhole 15 0099 to 15 0098
MH: 15 0099MH: 15 0098downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED0 ft. AMH - Upstream Manhole, Survey Begins - 15 00990 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area4.4 ft. RFJ - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YES31.8 ft. RFJ - Roots Fine Joint, from 12 to 02 o'clock, within 8 inches of joint: YES33.9 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start34.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"37.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"38 ft. RMJ - Roots Medium Joint, from 07 to 10 o'clock, 25 %, within 8 inches of joint: YESR85.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"85.4 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish88 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"133.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"135.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"183.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"186.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"218.4 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES234.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"237.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"256.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES269.1 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES278.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"281.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"284 ft. MGO - General Observation - 5% GREASE THROUGHOUT THE REACH, FROM 03 TO 09 O'CLOCK285.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED285.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED285.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0098

Observation photos (6)

  • Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YES

    4.4 ft. - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 12 to 02 o'clock, within 8 inches of joint: YES

    31.8 ft. - Roots Fine Joint, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    33.9 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    218.4 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    256.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    269.1 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

Observations (29)

DistanceCodeObservation
37.2TFC
234.6TF
284MGO5% GREASE THROUGHOUT THE REACH, FROM 03 TO 09 O'CLOCK
0MWM
135.5TFC
183.8TF
237.2TFC
281.4TFC
269.1CL
88TFC
0MGOCONNECTION AT MH 3 O'CLOCK CAPPED
0AMH15 0099
31.8RFJ
0MGOCONNECTION AT MH 9 O'CLOCK
285.2MGOCONNECTION AT MH 9 O'CLOCK CAPPED
34.6TFC
186.4TFC
85.4TFC
285.2MGOCONNECTION AT MH 3 O'CLOCK CAPPED
218.4CS
38RMJ
0MWL
4.4RFJ
133.2TFC
33.9RFJ
285.2AMH15 0098
278.8TFC
85.4RFJ
256.8FM

Properties (4)

additional_info
SC358720
custom_field_two
3
customer
LACSD
datetime
2018-03-29T03:01:27-07:00