Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 10, 2018, 07:36 AM
  • 18 0369_18 0368_4102018_023730.mp4

Date
04/10/2018
W/O
0699679
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00690
PipeID
P14203
Time
12:36 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0814
Sewer Name
18 NORTH NORWALK TRUNK
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
30
Purpose
Routine Assessment
Project
20180410MDM_NORTH_NORWALK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
18 0369
Downstream MH
18 0368
Dir. of Survey
Downstream
Length Surveyed
134.8 ft.
Total Length
134.8 ft.
Structural Index
2
Structural Quick
322B
Structural Rating
32
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
32
Pipe schematic from manhole 18 0369 to 18 0368
MH: 18 0369MH: 18 0368downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:25AM2.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE7.5 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - H11.3 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SLIGHT11.3 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL15.8 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - H15.8 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - H19.6 ft. FC - Fracture Circumferential, from 08 to 02 o'clock, within 8 inches of joint: YES - SL23.5 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H23.5 ft. FC - Fracture Circumferential, from 08 to 02 o'clock, within 8 inches of joint: YES - SL27.7 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL27.7 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL32 ft. MGO - General Observation - 15" VCP32 ft. FL - Fracture Longitudinal, at 08 TO 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS32 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS32 ft. FL - Fracture Longitudinal, at 08 TO 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS32 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS44.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open134.1 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 60% SLIGHT AT JOINTS134.1 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 60% HAIRLINE AT JOINTS134.1 ft. FL - Fracture Longitudinal, at 08 TO 04 o'clock, within 8 inches of joint: YES, Finish - 15% SLIGHT AT JOINTS134.1 ft. FL - Fracture Longitudinal, at 08 TO 04o'clock, within 8 inches of joint: YES, Finish - 15% HAIRLINE AT JOINTS134.8 ft. AMH - Downstream Manhole, Survey Ends - 2:50AM

Observation photos (1)

  • General Observation - 15" VCP

    32 ft. - General Observation - 15" VCP

Observations (25)

DistanceCodeObservation
32MGO15" VCP
15.8FCH
11.3FCSLIGHT
134.1FC60% SLIGHT AT JOINTS
44.7TFOpen
11.3FCSL
27.7FCSL
0MWM
134.1FC60% HAIRLINE AT JOINTS
23.5FCH
7.5FCH
32FLHAIRLINE AT JOINTS
27.7FCSL
134.8AMH2:50AM
15.8FCH
0MWL
134.1FL15% SLIGHT AT JOINTS
134.1FL15% HAIRLINE AT JOINTS
19.6FCSL
32FCSLIGHT AT JOINTS
32FLSLIGHT AT JOINTS
23.5FCSL
2.7FCHAIRLINE
0AMH2:25AM
32FCHAIRLINE AT JOINTS

Properties (4)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2018-04-10T00:36:15-07:00