Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 9, 2018, 08:32 AM
  • 05 1478_05 1477_492018_014410.mp4

Date
04/09/2018
W/O
0699845
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00438
PipeID
P06702
Time
1:32 AM
Certificate
U-1014-0602253
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Heavy Cleaning
Media Label
H0810
Sewer Name
05 EL NIDO TRUNK
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
23
Purpose
Maintenance Related
Project
20180407MDM_EL_NIDO_TRUNK
Material
NRCP
Shape
Circular
Height
12 in.
Upstream MH
05 1478
Downstream MH
05 1477
Dir. of Survey
Downstream
Length Surveyed
312.8 ft.
Total Length
312.8 ft.
Structural Index
2
Structural Quick
2300
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 05 1478 to 05 1477
MH: 05 1478MH: 05 1477downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 1:35AM2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MULTI LAYER PEELING CPNCRETE SEVERE AGG ATTACHED8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE92.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped144.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped165.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped196.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped244.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped296.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped310.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - MULTI LAYER PEELING CONCRETE SEVERE AGG ATTACHED312.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - MULTILAYER PEELING CONCRETE SEVERE AGG ATTACHED312.4 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN312.4 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped312.8 ft. AMH - Downstream Manhole, Survey Ends - 2:00AM

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MULTI LAYER PEELING CPNCRETE SEVERE AGG ATTACHED

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MULTI LAYER PEELING CPNCRETE SEVERE AGG ATTACHED

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - MULTI LAYER PEELING CONCRETE SEVERE AGG ATTACHED

    310.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - MULTI LAYER PEELING CONCRETE SEVERE AGG ATTACHED

Observations (17)

DistanceCodeObservation
244.9TFCCapped
196.2TFCCapped
165.9TFCCapped
92.5TFCCapped
0MWL
312.4SSSMULTILAYER PEELING CONCRETE SEVERE AGG ATTACHED
0MWM
8SSSPEELING CONCRETE
312.4MGOConn. @ Mh, 9 O' Clock. OPEN
310.3SSSMULTI LAYER PEELING CONCRETE SEVERE AGG ATTACHED
296.9TFCCapped
2SSSMULTI LAYER PEELING CPNCRETE SEVERE AGG ATTACHED
144.6TFCCapped
312.8AMH2:00AM
312.4MGOConn. @ Mh, 3 O' Clock. Capped
0MGOConn. @ Mh, 9 O' Clock. Active
0AMH1:35AM

Properties (4)

custom_field_three
MULTILAYER PEELING CONCRETE SEVERE AGG ATTACHED
custom_field_two
1
customer
LACSD
datetime
2018-04-09T01:32:18-07:00