Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 12, 2016, 07:52 AM
  • 32 1222_32 1221_12042016_005222.mp4

Date
04/12/2016
W/O
563392
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00843
PipeID
P19676
Time
12:52 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3314
Sewer Name
32 SOLEDAD CANYON RELIEF TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
05
Purpose
Routine Assessment
Project
WO_563392_TV32023_APRIL2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
32 1222
Downstream MH
32 1221
Dir. of Survey
Downstream
Length Surveyed
505.2 ft.
Total Length
505.2 ft.
Structural Index
3
Structural Quick
3S00
Structural Rating
300
O&M Index
2
O&M Quick
2S00
O&M Rating
200
Overall Index
3
Overall Quick
Overall Rating
500
Pipe schematic from manhole 32 1222 to 32 1221
MH: 32 1222MH: 32 1221downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 12222 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2.8 ft. MGO - General Observation - MAG COATING 60%2.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start324.6 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"502.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish502.7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish505.2 ft. AMH - Downstream Manhole, Survey Ends - 32 1221

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
2.8MGOMAG COATING 60%
0MWL
324.6TBA
2DAGS
502.7DAGS
2.8SAV
0MWM
0AMH32 1222
505.2AMH32 1221
502.7SAV

Properties (5)

additional_info
SC305441
custom_field_two
3
customer
LACSD
datetime
2016-04-12T00:52:03-07:00
year_laid
19730503