Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 15, 2016, 10:27 AM
  • 32 1192_32 1191_15042016_032806.mp4

Date
04/15/2016
W/O
563392
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00843
PipeID
P19646
Time
3:27 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3317
Sewer Name
32 SOLEDAD CANYON RELIEF TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
05
Purpose
Routine Assessment
Project
WO_563392_TV32023_APRIL2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
32 1192
Downstream MH
32 1191
Dir. of Survey
Downstream
Length Surveyed
500.2 ft.
Total Length
500.2 ft.
Structural Index
3
Structural Quick
3S00
Structural Rating
294
O&M Index
2
O&M Quick
2S00
O&M Rating
200
Overall Index
2
Overall Quick
Overall Rating
494
Pipe schematic from manhole 32 1192 to 32 1191
MH: 32 1192MH: 32 1191downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 11920 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start10.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start17.8 ft. MGO - General Observation - MAG COATING 70%369.7 ft. MGO - General Observation - RUN LIST STATES MH AT 371'.500.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish500.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish500.2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK500.2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK500.2 ft. AMH - Downstream Manhole, Survey Ends - 32 1191

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10.2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0AMH32 1192
17.8MGOMAG COATING 70%
369.7MGORUN LIST STATES MH AT 371'.
10.2SAV
500.2SAV
500.2DAGS
2DAGS
500.2MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0MWL
500.2MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWM
500.2AMH32 1191

Properties (5)

additional_info
SC305444
custom_field_two
3
customer
LACSD
datetime
2016-04-15T03:27:29-07:00
year_laid
19730727