Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 8, 2016, 10:25 AM
  • 32 1207_32 1206_08042016_034541.mp4

Date
04/08/2016
W/O
563392
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00843
PipeID
P19661
Time
3:25 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3312
Sewer Name
32 SOLEDAD CANYON RELIEF TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
05
Purpose
Routine Assessment
Project
WO_563392_TV32023_APRIL2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
32 1207
Downstream MH
32 1206
Dir. of Survey
Downstream
Length Surveyed
373.7 ft.
Total Length
373.7 ft.
Structural Index
3
Structural Quick
3N00
Structural Rating
222
O&M Index
2
O&M Quick
412N
O&M Rating
152
Overall Index
3
Overall Quick
Overall Rating
374
Pipe schematic from manhole 32 1207 to 32 1206
MH: 32 1207MH: 32 1206downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 12070 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. MGO - General Observation - MAG COATING 80%2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start372.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish372.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish373.7 ft. AMH - Downstream Manhole, Survey Ends - 32 1206

Observation photos (2)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
2MGOMAG COATING 80%
373.7AMH32 1206
2SAV
372.2DAGS
2DAGS
0AMH32 1207
0MWL
0MWM
372.2SAV

Properties (5)

additional_info
SC305439
custom_field_two
3
customer
LACSD
datetime
2016-04-08T03:25:11-07:00
year_laid
19730727