Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 7, 2016, 07:01 AM
  • B 0697_B 0696 _06122016_230400.mp4

Date
12/06/2016
W/O
607802
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00110
PipeID
P09367
Time
11:01 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
3844
Sewer Name
B JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
08
Purpose
Routine Assessment
Project
WO_607802_TV22155_DEC2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
B 0697
Downstream MH
B 0696
Dir. of Survey
Downstream
Length Surveyed
389.8 ft.
Total Length
389.8 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
186
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
187
Pipe schematic from manhole B 0697 to B 0696
MH: B 0697MH: B 0696downstream0 ft. MGO - General Observation - CONNECTION AT THE MH CAPPED 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - B 06970 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area3.2 ft. MGO - General Observation - MAG COAT44.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"50.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"73.8 ft. RFL - Roots Fine Lateral, at 10 o'clock73.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.6 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start80.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"167.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"170.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"200.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"203.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"257.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"266.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"305.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"308.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"387.7 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish389.8 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK389.8 ft. AMH - Downstream Manhole, Survey Ends - B 0696389.8 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK

Observation photos (2)

  • Roots Fine Lateral, at 10 o'clock

    73.8 ft. - Roots Fine Lateral, at 10 o'clock

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    75.6 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
0MGOCONNECTION AT THE MH CAPPED 3 O'CLOCK
387.7SAV
305.2TFC
389.8MGOCONNECTION AT THE MH 9 O'CLOCK
257.4TF
266.5TF
50.3TF
73.8RFL
0AMHB 0697
167.2TFC
80.2TFC
44.1TFC
75.6SAV
0MWM
389.8AMHB 0696
170.2TF
203.2TFC
308.1TF
3.2MGOMAG COAT
0MWL
200.3TF
389.8MGOCONNECTION AT THE MH 3 O'CLOCK
73.8TF

Properties (4)

additional_info
SC304594
custom_field_two
3
customer
LACSD
datetime
2016-12-06T23:01:05-08:00