Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 7, 2016, 10:12 AM
  • B 0720_B 0719 _07122016_021300.mp4

Date
12/07/2016
W/O
607802
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00110
PipeID
P09394
Time
2:12 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
3844
Sewer Name
B JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
08
Purpose
Routine Assessment
Project
WO_607802_TV22155_DEC2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
B 0720
Downstream MH
B 0719
Dir. of Survey
Downstream
Length Surveyed
412.6 ft.
Total Length
412.6 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
246
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
246
Pipe schematic from manhole B 0720 to B 0719
MH: B 0720MH: B 0719downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 07200 ft. MWL - Water Level, 10 %of cross sectional area2.3 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start2.3 ft. MGO - General Observation - MAG COAT23 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"74.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"122.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"174.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"222.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"274.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"322.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"412 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish412.6 ft. MGO - General Observation - CONNECTION AT THE MH CAPPED 12 O'CLOCK412.6 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK412.6 ft. AMH - Downstream Manhole, Survey Ends - B 0719

Observation photos (1)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
122.8TFC
0MWM
0AMHB 0720
274.1TFC
222.8TFC
412.6MGOCONNECTION AT THE MH CAPPED 12 O'CLOCK
322.5TFC
2.3SAV
412SAV
412.6MGOCONNECTION AT THE MH 3 O'CLOCK
2.3MGOMAG COAT
412.6AMHB 0719
174.6TFC
0MWL
23TFC
74.4TFC

Properties (4)

additional_info
SC304594
custom_field_two
3
customer
LACSD
datetime
2016-12-07T02:12:18-08:00