Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2018, 07:27 AM
  • 01 0047A_01 0047_01032018_004453.mp4

Date
02/28/2018
W/O
691313
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00711
Time
11:27 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5470
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
WO_691313_TV01255_MAR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0047A
Downstream MH
01 0047
Dir. of Survey
Downstream
Length Surveyed
326.6 ft.
Total Length
326.6 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
186
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
186
Pipe schematic from manhole 01 0047A to 01 0047
MH: 01 0047AMH: 01 0047downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 01 0047A0 ft. MGO - General Observation - COCKROACHES IN MANHOLE15.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start63.7 ft. TFA - Tap Factory Made Active, Defective at 11 o'clock, -, within 8 inches of joint: NO, 4" - GAP IN TAP PIPING67 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 4"116.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 4"118.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 4"174.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"177.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 4"225.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"228.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 4"269.1 ft. TFC - Tap Factory Made Capped, Defective at 02 o'clock, -, within 8 inches of joint: NO, 4" - CRACKED CAP271.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"308.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"310.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 4"324.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE324.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish326.6 ft. MGO - General Observation - ACTIVE CONNECTIONS AT 3 AND 9 O'CLOCK326.6 ft. AMH - Downstream Manhole, Survey Ends - 01 0047

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
0MWL
326.6MGOACTIVE CONNECTIONS AT 3 AND 9 O'CLOCK
271.5TFC
324.6MGOCOCKROACHES IN MANHOLE
308.4TFC
63.7TFAGAP IN TAP PIPING
0MWM
174.3TFC
15.7CM
225.9TFC
0MGOACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK
177.3TFC
326.6AMH01 0047
118.8TFC
310.5TFC
228.9TFC
0AMH01 0047A
116.9TFC
67TFC
324.6CM
269.1TFCCRACKED CAP
0MGOCOCKROACHES IN MANHOLE

Properties (4)

additional_info
SC358476
custom_field_two
2
customer
LACSD
datetime
2018-02-28T23:27:32-08:00