Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 2, 2018, 07:25 AM
  • 01 0051_01 0050A_02032018_004508.mp4

Date
03/01/2018
W/O
691313
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00209
PipeID
P00718
Time
11:25 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5471
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_691313_TV01255_MAR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0051
Downstream MH
01 0050A
Dir. of Survey
Downstream
Length Surveyed
277.3 ft.
Total Length
277.3 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
153
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
153
Pipe schematic from manhole 01 0051 to 01 0050A
MH: 01 0051MH: 01 0050Adownstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 005124.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start58.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 4"112.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 4"113.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 4"238.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 4"241.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 4"277.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish277.3 ft. AMH - Downstream Manhole, Survey Ends - 01 0050A277.3 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    24.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWL
277.3CM
0AMH01 0051
113.9TFC
58.8TFC
238.9TFC
112.1TFC
241.1TFC
277.3AMH01 0050A
24.5CM
277.3MGOACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK

Properties (4)

additional_info
SC358477
custom_field_two
3
customer
LACSD
datetime
2018-03-01T23:25:30-08:00