Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 4, 2018, 11:34 AM
  • 08 0536_08 0535_442018_044710.mp4

Date
04/04/2018
W/O
0699100
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00021
PipeID
P00598
Time
4:34 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0802
Sewer Name
08 VICTORIA STREET TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20180403MDM_VICTORIA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
08 0536
Downstream MH
08 0535
Dir. of Survey
Downstream
Length Surveyed
276.7 ft.
Total Length
276.7 ft.
Structural Index
2
Structural Quick
4237
Structural Rating
93
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
93
Pipe schematic from manhole 08 0536 to 08 0535
MH: 08 0536MH: 08 0535downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:45AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active8 ft. MGO - General Observation - 10" VCP14.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SLIGHT38.7 ft. FC - Fracture Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES - SL51.2 ft. FC - Fracture Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES - HAIRLINE55.1 ft. FC - Fracture Circumferential, from 08 to 01 o'clock, within 8 inches of joint: YES - SL59.2 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H63.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL67.3 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H67.3 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H79.7 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL83.7 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL83.7 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL83.7 ft. B - Broken, from 09 to 10 o'clock, within 8 inches of joint: YES - SLIGHT CIRCUM FRACTURE87.9 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H96 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL96 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL108.2 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - H120.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL136.5 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL144.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL144.7 ft. FC - Fracture Circumferential, from 11 to 04 o'clock, within 8 inches of joint: YES - SL153.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H165 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL165 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H185.4 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H185.4 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H189.3 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL189.3 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL205.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H213.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H213.6 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES217.7 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H226.2 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT226.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: NO - H233.9 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES - SPORATIC THROUGHOUT REACH246.5 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H246.5 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL250.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H250.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SL254.6 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL262.7 ft. FC - Fracture Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES - H270.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL276.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active276.2 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active276.7 ft. AMH - Downstream Manhole, Survey Ends - 5:30AM

Observation photos (6)

  • General Observation - 10" VCP

    8 ft. - General Observation - 10" VCP

  • Broken, from 09 to 10 o'clock, within 8 inches of joint: YES - SLIGHT CIRCUM FRACTURE

    83.7 ft. - Broken, from 09 to 10 o'clock, within 8 inches of joint: YES - SLIGHT CIRCUM FRACTURE

  • Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES

    213.6 ft. - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

    226.2 ft. - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

  • Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES - SPORATIC THROUGHOUT REACH

    233.9 ft. - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES - SPORATIC THROUGHOUT REACH

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

    270.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

Observations (49)

DistanceCodeObservation
185.4FLH
83.7FCSL
250.5FLH
226.9FCH
276.7AMH5:30AM
144.7FCSL
136.5FCSL
165FCSL
144.7FCSL
213.6FLH
83.7FCSL
250.5FLSL
67.3FCH
153.1FCH
51.2FCHAIRLINE
96FCSL
217.7FLH
276.2MGOConn. @ Mh, 3 O' Clock. Active
189.3FCSL
67.3FCH
262.7FCH
14.1FCSLIGHT
0MWM
276.2MGOConn. @ Mh, 9 O' Clock. Active
205.7FLH
246.5FCH
79.7FCSL
226.2FCSLIGHT
55.1FCSL
270.7FMSL
38.7FCSL
120.4FCSL
254.6FCSL
0MWL
59.2FCH
8MGO10" VCP
108.2FCH
83.7BSLIGHT CIRCUM FRACTURE
189.3FCSL
96FCSL
165FCH
63.1FCSL
246.5FCSL
0AMH4:45AM
185.4FLH
233.9SSSSPORATIC THROUGHOUT REACH
87.9FCH
213.6SSS
0MGOConn. @ Mh, 9 O' Clock. Active

Properties (4)

custom_field_three
BROKEN PIPE SMALL CIRCUM FRACTURE
custom_field_two
2
customer
LACSD
datetime
2018-04-04T04:34:40-07:00