Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 24, 2018, 08:35 AM
  • 14 0464_14 0463 _24012018_005234.mp4

Date
01/24/2018
W/O
685065
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00580
PipeID
P18553
Time
12:35 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5384
Sewer Name
14 TRUNK "D"
City
LANCASTER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
21
Purpose
Routine Assessment
Project
WO_685065_TV14023_FEB2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
14 0464
Downstream MH
14 0463
Dir. of Survey
Downstream
Length Surveyed
341.2 ft.
Total Length
341.2 ft.
Structural Index
2
Structural Quick
342L
Structural Rating
146
O&M Index
2
O&M Quick
412L
O&M Rating
138
Overall Index
2
Overall Quick
Overall Rating
284
Pipe schematic from manhole 14 0464 to 14 0463
MH: 14 0464MH: 14 0463downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 04640 ft. MWM - Water Mark, 60 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start31.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"109.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"182.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"206.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"231.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"255.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"283 ft. MGO - General Observation - POSSIBLY MISSED CONNECTION OBSERVATION @ 2 OC307.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"318.9 ft. H - Hole, at 12 o'clock, within 8 inches of joint: YES - HOLE/MISSING WALL327 ft. H - Hole, at 12 o'clock, within 8 inches of joint: YES - HOLE/MISSING WALL330 ft. MGO - General Observation - POSSIBLE HOLE/MISSING WALL @ 12 OC335.1 ft. H - Hole, at 12 o'clock, within 8 inches of joint: YES - HOLE/MISSING WALL339.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish339.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish339.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish341.2 ft. AMH - Downstream Manhole, Survey Ends - 14 0463

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Hole, at 12 o'clock, within 8 inches of joint: YES - HOLE/MISSING WALL

    318.9 ft. - Hole, at 12 o'clock, within 8 inches of joint: YES - HOLE/MISSING WALL

  • Hole, at 12 o'clock, within 8 inches of joint: YES - HOLE/MISSING WALL

    327 ft. - Hole, at 12 o'clock, within 8 inches of joint: YES - HOLE/MISSING WALL

  • Hole, at 12 o'clock, within 8 inches of joint: YES - HOLE/MISSING WALL

    335.1 ft. - Hole, at 12 o'clock, within 8 inches of joint: YES - HOLE/MISSING WALL

Observations (22)

DistanceCodeObservation
339.2SAP
307.8TFC
255.4TFC
31.8TFC
0MWL
341.2AMH14 0463
206.8TFC
0AMH14 0464
2DAGS
182.6TFC
283MGOPOSSIBLY MISSED CONNECTION OBSERVATION @ 2 OC
0MWM
231.3TFC
109.2TFC
330MGOPOSSIBLE HOLE/MISSING WALL @ 12 OC
318.9HHOLE/MISSING WALL
2SAP
339.2DAGS
2SSS
327HHOLE/MISSING WALL
335.1HHOLE/MISSING WALL
339.2SSS

Properties (4)

additional_info
SC346963
custom_field_two
1
customer
LACSD
datetime
2018-01-24T00:35:17-08:00