Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 23, 2018, 11:31 AM
  • Section#3_F 0218_F 0217__3232018__G6980.mp4

Date
03/23/2018
W/O
0687463
Weather
Light Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00050
PipeID
P10348
Time
4:31 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6980
Sewer Name
F JOINT OUTFALL F - UNIT 7H
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
38
Purpose
Routine Assessment
Project
20180322MDM_JOINT_OUTFALL_F_UNIT_7H
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
F 0218
Downstream MH
F 0217
Dir. of Survey
Downstream
Length Surveyed
411.7 ft.
Total Length
411.7 ft.
Structural Index
3
Structural Quick
3P2O
Structural Rating
419
O&M Index
5
O&M Quick
5141
O&M Rating
9
Overall Index
3
Overall Quick
Overall Rating
428
Pipe schematic from manhole F 0218 to F 0217
MH: F 0218MH: F 0217downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - MH CONN 9:00 ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 5:40AM2 ft. MGO - General Observation - MAG COAT 30% START 8:00 TO 4:002 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC30.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERTE AGG SPORATIC30.6 ft. MGO - General Observation - MAG COAT 70% START45 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB109.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC109.4 ft. MGO - General Observation - MAG COAT 20% START110 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE161.8 ft. MWM - Water Mark, 30 %of cross sectional area192.3 ft. SAV - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: YES - SEVERE AGG203 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB236.1 ft. MWM - Water Mark, 50 %of cross sectional area303.9 ft. MWM - Water Mark, 80 %of cross sectional area303.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB303.9 ft. MWL - Water Level, 40 %of cross sectional area411.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING CONCRETE411.1 ft. MGO - General Observation - MAG COAT 20% FINISH411.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC411.7 ft. AMH - Downstream Manhole, Survey Ends - 6:35AM

Observation photos (10)

  • General Observation - MAG COAT 30% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 30% START 8:00 TO 4:00

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERTE AGG SPORATIC

    30.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERTE AGG SPORATIC

  • General Observation - MAG COAT 70% START

    30.6 ft. - General Observation - MAG COAT 70% START

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    109.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • General Observation - MAG COAT 20% START

    109.4 ft. - General Observation - MAG COAT 20% START

  • Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: YES - SEVERE AGG

    192.3 ft. - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Water Mark, 50 %of cross sectional area

    236.1 ft. - Water Mark, 50 %of cross sectional area

  • Water Mark, 80 %of cross sectional area

    303.9 ft. - Water Mark, 80 %of cross sectional area

Observations (24)

DistanceCodeObservation
303.9MWM
161.8MWM
236.1MWM
303.9TFCSTUB
411.1SSSBLISTERING CONCRETE
30.6SAVSEVERTE AGG SPORATIC
0MWM
411.1MGOMAG COAT 20% FINISH
2MGOMAG COAT 30% START 8:00 TO 4:00
303.9MWL
0MWL
45TFCSTUB
192.3SAVSEVERE AGG
110TFACTIVE
411.1SAVSEVERE AGG SPORATIC
109.4SAVSEVERE AGG SPORATIC
2SSSBLISTERING CONCRETE
411.7AMH6:35AM
203TFCSTUB
2SAVSEVERE AGG SPORATIC
0MGOMH CONN 9:00 ACTIVE
30.6MGOMAG COAT 70% START
0AMH5:40AM
109.4MGOMAG COAT 20% START

Properties (4)

custom_field_three
SEVERE AGG VISIBLE SPORATIC-BLISTERING CONCRETE
custom_field_two
4
customer
LACSD
datetime
2018-03-23T04:31:42-07:00