Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 13, 2018, 05:29 AM
  • 01 0540_01 0539_12032018_224837.mp4

Date
03/12/2018
W/O
690113
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00206
PipeID
P01028
Time
10:29 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5481
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_690113_TV01232_MAR2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
01 0540
Downstream MH
01 0539
Dir. of Survey
Downstream
Length Surveyed
315.7 ft.
Total Length
315.7 ft.
Structural Index
3
Structural Quick
3L22
Structural Rating
193
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
193
Pipe schematic from manhole 01 0540 to 01 0539
MH: 01 0540MH: 01 0539downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 05402 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES71.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"79.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"89.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"126.6 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES147.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"155.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"193.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"210.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"243.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"254.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"288.3 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES297.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"300.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"313.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish315.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE315.7 ft. AMH - Downstream Manhole, Survey Ends - 01 0539

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    5 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    126.6 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    288.3 ft. - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
297.5TFC
315.7MGOCOCKROACHES IN MANHOLE
315.7AMH01 0539
155.5TF
300.1TF
0MGOCOCKROACHES IN MANHOLE
0MWL
313.4SAP
147.8TF
254.4TFC
210.1TFC
126.6CL
0AMH01 0540
79.4TFC
243.8TF
5CL
288.3CM
193.6TF
89.4TFC
71.8TFA
2SAP

Properties (4)

additional_info
SC358487
custom_field_two
2
customer
LACSD
datetime
2018-03-12T22:29:22-07:00