Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 1, 2018, 09:10 AM
  • 02 2227_02 2226_01022018_022012.mp4

Date
02/01/2018
W/O
684901
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00253
PipeID
P04501
Time
1:10 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5395
Sewer Name
02 DOWNEY-BELLFLOWER DIVERSION RELIEF TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
24
Purpose
Routine Assessment
Project
WO_684901_TV02051_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
02 2226
Downstream MH
02 2227
Dir. of Survey
Upstream
Length Surveyed
325.4 ft.
Total Length
325.4 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 02 2226 to 02 2227
MH: 02 2226MH: 02 2227upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 22270 ft. MGO - General Observation - COCKROACHES IN MANHOLE321.4 ft. CS - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES325.4 ft. AMH - Downstream Manhole, Survey Begins - 02 2226325.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE325.4 ft. MWM - Water Mark, 25 %of cross sectional area325.4 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (1)

  • Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

    4 ft. - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
0AMH02 2226
325.4AMH02 2227
0MGOCOCKROACHES IN MANHOLE
0MWM
325.4MGOCOCKROACHES IN MANHOLE
0MWL
4CS

Properties (5)

additional_info
SC346974
custom_field_two
4
customer
LACSD
datetime
2018-02-01T01:10:43-08:00
year_laid
31440