Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 22, 2018, 10:43 AM
  • 05 1009_05 1044_3222018_034444.mp4

Date
03/22/2018
W/O
0694538
Weather
Light Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00421
PipeID
P06242
Time
3:43 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0787
Sewer Name
05 AVIATION BOULEVARD TRUNK
City
MANHATTAN BRACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
16
Purpose
Capital Improvement Program Assesment
Project
20180322MDM_AVIATION_BOULEVARD_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Upstream MH
05 1009
Downstream MH
05 1044
Dir. of Survey
Downstream
Length Surveyed
324.7 ft.
Total Length
324.7 ft.
Structural Index
4
Structural Quick
5A36
Structural Rating
72
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
4
Overall Quick
Overall Rating
74
Pipe schematic from manhole 05 1009 to 05 1044
MH: 05 1009MH: 05 1044downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:15AM0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE8 ft. MGO - General Observation - 21" RCP23.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC83.3 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR83.9 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC85.9 ft. SSS - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE120 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: NO - ROCKS139.5 ft. SRC - Surface Reinforcement Corroded, from 09 to 11 o'clock, within 8 inches of joint: YES, - CIRCUM REBAR182.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR183.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR186.9 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR188.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG212.1 ft. SAP - Surface Aggregate Projecting, from 08 to 12 o'clock, within 8 inches of joint: NO, Start - SEVEWRE AGG220.1 ft. SAP - Surface Aggregate Projecting, from 08 to 12 o'clock, within 8 inches of joint: NO, Finish - SEVERE AGG225.3 ft. SRV - Surface Reinforcement Visible, from 08 to 09 o'clock, within 8 inches of joint: NO - CIRCUM REBAR237.9 ft. SAP - Surface Aggregate Projecting, from 08 to 11 o'clock, within 8 inches of joint: NO - SEVEDRE AGGG269.7 ft. SRV - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR292.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG294.6 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR296.7 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR302.8 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM307.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR317.2 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR324.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG324.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE324.3 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active324.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC324.7 ft. AMH - Downstream Manhole, Survey Ends - 5:10AM

Observation photos (19)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - 21" RCP

    8 ft. - General Observation - 21" RCP

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    23.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    83.3 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC

    83.9 ft. - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC

  • Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    85.9 ft. - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Deposits Settled Other,  5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: NO - ROCKS

    120 ft. - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: NO - ROCKS

  • Surface Reinforcement Corroded, from 09 to 11 o'clock, within 8 inches of joint: YES,  - CIRCUM REBAR

    139.5 ft. - Surface Reinforcement Corroded, from 09 to 11 o'clock, within 8 inches of joint: YES, - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

    182.1 ft. - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    183.3 ft. - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    188.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Projecting, from 08 to 12 o'clock, within 8 inches of joint: NO, Start - SEVEWRE AGG

    212.1 ft. - Surface Aggregate Projecting, from 08 to 12 o'clock, within 8 inches of joint: NO, Start - SEVEWRE AGG

  • Surface Reinforcement Visible, from 08 to 09 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    225.3 ft. - Surface Reinforcement Visible, from 08 to 09 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    269.7 ft. - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    292.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    294.6 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    296.7 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM

    302.8 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    317.2 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

Observations (31)

DistanceCodeObservation
324.3SAPSEVERE AGG
0MWL
0AMH4:15AM
120DSZROCKS
324.7AMH5:10AM
212.1SAPSEVEWRE AGG
292.4SAPSEVERE AGG
269.7SRVCIRCUM REBAR
23.9SAVSEVERE AGG SPORATIC
237.9SAPSEVEDRE AGGG
2SSSBLISTERING PEELING CONCRETE
139.5SRCCIRCUM REBAR
220.1SAPSEVERE AGG
324.3SSSBLISTERING PEELING CONCRETE
186.9SRCCIRCUM REBAR
85.9SSSPEELING CONCRETE
294.6SRVCIRCUM REBAR
83.3SRVCIRCUM REBAR
225.3SRVCIRCUM REBAR
307.1SRVCIRCUM REBAR
324.3MGOConn. @ Mh, 9 O' Clock. Active
302.8SRVCIRCUM
296.7SRVCIRCUM REBAR
8MGO21" RCP
0MWM
183.3SRCCIRCUM REBAR
317.2SRVCIRCUM REBAR
324.3SAVSEVERE AGG SPORATIC
188.3SAVSEVERE AGG
83.9SAVSEVERE AGG SPORATIC
182.1SRCCIRCUM REBAR

Properties (4)

custom_field_three
CORRODED CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2018-03-22T03:43:17-07:00