Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 21, 2018, 03:32 PM
  • G 0094_E 0020_3212018_095601.mp4

Date
03/21/2018
W/O
PENDING
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00027
PipeID
P07607
Time
8:32 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0785
Sewer Name
E JOINT OUTFALL E - UNIT 1
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
20
Purpose
Routine Assessment
Project
20180321SHO_JOINT_OUTFALL_E_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Upstream MH
G 0094
Downstream MH
E 0020
Dir. of Survey
Downstream
Length Surveyed
18.7 ft.
Total Length
18.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole G 0094 to E 0020
MH: G 0094MH: E 0020downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 09550 ft. MWM - Water Mark, 15 %of cross sectional area13 ft. MGO - General Observation - 95% MAG COAT INTACT16.1 ft. DSC - Deposits Settled Compacted, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO18.7 ft. MSA - Survey Abandoned - DUE TO DEBRIS IN THE LINE

Observation photos (1)

  • Deposits Settled Compacted,  15 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO

    16.1 ft. - Deposits Settled Compacted, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO

Observations (6)

DistanceCodeObservation
16.1DSC
0MWL
0AMH0955
13MGO95% MAG COAT INTACT
18.7MSADUE TO DEBRIS IN THE LINE
0MWM

Properties (5)

additional_info
NOT AN ACTIVE LINE
custom_field_three
INSPECTION NOT COMPLETE DUE TO DEBRIS
custom_field_two
5
customer
LACSD
datetime
2018-03-21T08:32:48-07:00