Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2018, 12:07 PM
  • Section#2_B 0184A_B 0184__3172018__G6978.mp4

Date
03/17/2018
W/O
0694534
Weather
Light Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00075
PipeID
P08669
Time
5:07 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6978
Sewer Name
B JOINT OUTFALL B - UNIT 1D
City
PICO RIVERA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
19
Purpose
Capital Improvement Program Assesment
Project
20180317MDM_JOINT_OUTFALL_B_UNIT_1D
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Upstream MH
B 0184A
Downstream MH
B 0184
Dir. of Survey
Downstream
Length Surveyed
534.7 ft.
Total Length
534.7 ft.
Structural Index
5
Structural Quick
5_4T
Structural Rating
1214
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
1218
Pipe schematic from manhole B 0184A to B 0184
MH: B 0184AMH: B 0184downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 6:30AM0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG42.5 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUM42.5 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM65 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR65 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR65 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR78.4 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR78.4 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR192.7 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR301.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR301.8 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR301.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish - CIRCUM REBAR534.2 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO, Finish534.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG534.2 ft. MGO - General Observation - MH CONN 9:00 OPEN TOP OF STACK534.7 ft. AMH - Downstream Manhole, Survey Ends - 7:20AM

Observation photos (9)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    42.5 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    65 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR

    65 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

    78.4 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    78.4 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    192.7 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

    301.8 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

Observations (20)

DistanceCodeObservation
78.4SRCCIRCUM REBAR
0MWL
65SRCCIRCUM REBAR
534.2SRC
42.5SRVCIRCUM
301.8SRCCIRCUM REBAR
534.2SAMSEVERE AGG
301.8SRCCIRCUM REBAR
534.7AMH7:20AM
534.2MGOMH CONN 9:00 OPEN TOP OF STACK
301.8SRCCIRCUM REBAR
0AMH6:30AM
78.4SRCCIRCUM REBAR
0MWM
65SRCCIRCUM REBAR
192.7SRCCIRCUM REBAR
42.5SRCCIRCUM
2SRVCIRCUM REBAR
2SAMSEVERE AGG
65SRVCIRCUM REBAR

Properties (4)

custom_field_three
CORRODED CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2018-03-17T05:07:18-07:00