Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 16, 2018, 08:20 AM
  • Section#1_H 0345_H 0344__3162018__G6973.mp4

Date
03/16/2018
W/O
0694533
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00176
PipeID
P10794
Time
1:20 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6973
Sewer Name
H JOINT OUTFALL H - UNIT 4 RELIEF
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
19
Purpose
Routine Assessment
Project
20180316MDM_JOINT_OUTFALL_H_UNIT_4_RELIEF
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Upstream MH
H 0345
Downstream MH
H 0344
Dir. of Survey
Downstream
Length Surveyed
568.7 ft.
Total Length
568.7 ft.
Structural Index
2
Structural Quick
3P2V
Structural Rating
479
O&M Index
3
O&M Quick
413Q
O&M Rating
320
Overall Index
3
Overall Quick
Overall Rating
799
Pipe schematic from manhole H 0345 to H 0344
MH: H 0345MH: H 0344downstream0 ft. MWM - Water Mark, 50 %of cross sectional area - NORMAL 20%0 ft. AMH - Upstream Manhole, Survey Begins - 1:20AM0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 80% START 9:00 TO 3:002 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start37.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE64.8 ft. MGO - General Observation - MAG COAT 60% START117 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish117 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start134.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE159.1 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG166.5 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG VERY SPORATIC261.9 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG VERY SPORATIC299.7 ft. MGO - General Observation - 57" RCP401.6 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC568.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING CONCRETE568.2 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish568.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish - SEVERE AGG VERY SPORATIC568.7 ft. AMH - Downstream Manhole, Survey Ends - 2:20AM

Observation photos (12)

  • General Observation - MAG COAT 80% START 9:00 TO 3:00

    2 ft. - General Observation - MAG COAT 80% START 9:00 TO 3:00

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    37.4 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • General Observation - MAG COAT 60% START

    64.8 ft. - General Observation - MAG COAT 60% START

  • Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    117 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    134.4 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    159.1 ft. - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG VERY SPORATIC

    166.5 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG VERY SPORATIC

  • Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG VERY SPORATIC

    261.9 ft. - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG VERY SPORATIC

  • General Observation - 57" RCP

    299.7 ft. - General Observation - 57" RCP

  • Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    401.6 ft. - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

Observations (20)

DistanceCodeObservation
134.4SSSBLISTERING CONCRETE
159.1SAVSEVERE AGG
117DAGS
568.2SSSBLISTERING CONCRETE
0MWMNORMAL 20%
2MGOMAG COAT 80% START 9:00 TO 3:00
37.4SSSBLISTERING CONCRETE
299.7MGO57" RCP
401.6SAVSEVERE AGG SPORATIC
0AMH1:20AM
568.7AMH2:20AM
0MWL
568.2DAGS
2SSSBLISTERING CONCRETE
64.8MGOMAG COAT 60% START
2DAGS
568.2SAVSEVERE AGG VERY SPORATIC
117DAGS
166.5SAVSEVERE AGG VERY SPORATIC
261.9SAVSEVERE AGG VERY SPORATIC

Properties (4)

custom_field_three
BLISTERING CONCRETE-VISIBLE SEVERE AGG VERY SPORAT
custom_field_two
4
customer
LACSD
datetime
2018-03-16T01:20:04-07:00