Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 26, 2018, 12:00 PM
Date
02/26/2018
W/O
685104
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00323
PipeID
P08083
Time
4:00 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5466
Sewer Name
A JOA-1A LOS COYOTES WRP INTERCEPTOR
City
CERRITOS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
WO_685104_TV30023_FEB2018
Sewer Type
Gravity
Material
RGRCP
Shape
Circular
Height
81 in.
Width
81 in.
Upstream MH
A 0146
Downstream MH
A 0927
Dir. of Survey
Downstream
Length Surveyed
94.9 ft.
Total Length
94.9 ft.
Structural Index
2
Structural Quick
2C00
Structural Rating
38
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
38
Pipe schematic from manhole A 0146 to A 0927
MH: A 0146MH: A 0927downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 01462 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start94.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish94.9 ft. AMH - Downstream Manhole, Survey Ends - A 0927

Observation photos (1)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (5)

DistanceCodeObservation
0MWL
2SSS
94.9SSS
0AMHA 0146
94.9AMHA 0927

Properties (4)

additional_info
SC358471
custom_field_two
3
customer
LACSD
datetime