Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 3, 2015, 08:29 AM
  • 20 0262_20 0261_03112015_002956.mp4

Date
11/03/2015
W/O
531056
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00753
PipeID
P19229
Time
12:29 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2820
Sewer Name
20 35TH STREET EAST TRUNK
City
PALMDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 20
Page No.
07
Purpose
Routine Assessment
Project
WO_531056_TV20009_OCT2015
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
10 in.
Upstream MH
20 0262
Downstream MH
20 0261
Dir. of Survey
Downstream
Length Surveyed
334.5 ft.
Total Length
334.5 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
198
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
3
Overall Quick
Overall Rating
330
Pipe schematic from manhole 20 0262 to 20 0261
MH: 20 0262MH: 20 0261downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 20 02620 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 04 to 08 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"54.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"106.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"154.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"206.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"253.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"306.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"332.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish332.9 ft. SAP - Surface Aggregate Projecting, from 04 to 08 o'clock, within 8 inches of joint: YES, Finish334.5 ft. AMH - Downstream Manhole, Survey Ends - 20 0261

Observation photos (1)

  • Surface Aggregate Projecting, from 04 to 08 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 04 to 08 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
106.4TFC
154.7TFC
2SAP
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMH20 0262
0MWM
206.1TFC
306.3TFC
0MWL
334.5AMH20 0261
332.9DAGS
253.7TFC
6.2TFC
2DAGS
54.5TFC
332.9SAP

Properties (4)

additional_info
SC204154
custom_field_two
3
customer
LACSD
datetime
2015-11-03T00:29:04-08:00