Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 10, 2016, 11:09 AM
  • 08 0258_08 0257 _08102016_042227.mp4

Date
08/10/2016
W/O
580478
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00004
PipeID
P00299
Time
4:09 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3631
Sewer Name
08 DEL AMO TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
08
Purpose
Routine Assessment
Project
WO_580478_TV08039_JULY2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
08 0258
Downstream MH
08 0257
Dir. of Survey
Downstream
Length Surveyed
282.5 ft.
Total Length
282.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
322T
O&M Rating
218
Overall Index
2
Overall Quick
Overall Rating
218
Pipe schematic from manhole 08 0258 to 08 0257
MH: 08 0258MH: 08 0257downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 02580 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start29 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start47.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"50.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"64.7 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES154.5 ft. ID - Infiltration Dripper, at 11 o'clock, within 8 inches of joint: NO156.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"159 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"280.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish280.8 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish282.5 ft. AMH - Downstream Manhole, Survey Ends - 08 0257282.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    29 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

    64.7 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, at 11 o'clock, within 8 inches of joint: NO

    154.5 ft. - Infiltration Dripper, at 11 o'clock, within 8 inches of joint: NO

  • General Observation - COCKROACHES IN MANHOLE

    282.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
156.9TFC
159TFC
282.5AMH08 0257
2DAGS
0MWM
280.8DAGS
282.5MGOCOCKROACHES IN MANHOLE
154.5ID
0AMH08 0258
50.9TFC
64.7ID
29DAE
280.8DAE
0MWL
47.9TFC

Properties (4)

additional_info
SC306065
custom_field_two
4
customer
LACSD
datetime
2016-08-10T04:09:09-07:00