Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2016, 07:22 AM
  • 08 0263_08 0262 _08122016_003203.mp4

Date
08/12/2016
W/O
580478
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00004
PipeID
P00304
Time
12:22 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3634
Sewer Name
08 DEL AMO TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
08
Purpose
Routine Assessment
Project
WO_580478_TV08039_JULY2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
08 0263
Downstream MH
08 0262
Dir. of Survey
Downstream
Length Surveyed
245.7 ft.
Total Length
245.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2O00
O&M Rating
162
Overall Index
2
Overall Quick
Overall Rating
165
Pipe schematic from manhole 08 0263 to 08 0262
MH: 08 0263MH: 08 0262downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 08 02630 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start8.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"8.4 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 10 o'clock, , within 8 inches of joint: YES11.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"21.2 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES69.3 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES86.9 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start125.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"128.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"243.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish243.7 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish245.7 ft. AMH - Downstream Manhole, Survey Ends - 08 0262245.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE245.7 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (7)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 10 o'clock,  , within 8 inches of joint: YES

    8.4 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 10 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 01 to 05 o'clock,  , within 8 inches of joint: YES

    21.2 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    69.3 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    86.9 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    245.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (18)

DistanceCodeObservation
8.3TFC
21.2DAE
11.9TFC
2DAGS
0MGOCOCKROACHES IN MANHOLE
243.7DAGS
125.2TFC
243.7DAE
0AMH08 0263
0MWL
0MWM
86.9DAE
245.7AMH08 0262
8.4DAE
245.7MGOCOCKROACHES IN MANHOLE
69.3CM
128.6TFC
245.7MGOACTIVE CONNECTION AT MH 9 O'CLOCK

Properties (4)

additional_info
SC306068
custom_field_two
4
customer
LACSD
datetime
2016-08-12T00:22:10-07:00