Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 13, 2018, 09:42 AM
  • Section#3_H 0351_H 0350__3132018__G6969.mp4

Date
03/13/2018
W/O
0694533
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00176
PipeID
P10800
Time
2:42 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6972
Sewer Name
H JOINT OUTFALL H - UNIT 4 RELIEF
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
19A
Purpose
Routine Assessment
Project
20180313MDM_JOINT_OUTFALL_H_UNIT_4_RELIEF
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Upstream MH
H 0351
Downstream MH
H 0350
Dir. of Survey
Downstream
Length Surveyed
1010.6 ft.
Total Length
1010.6 ft.
Structural Index
2
Structural Quick
2h00
Structural Rating
410
O&M Index
2
O&M Quick
412g
O&M Rating
408
Overall Index
2
Overall Quick
Overall Rating
818
Pipe schematic from manhole H 0351 to H 0350
MH: H 0351MH: H 0350downstream0 ft. MWM - Water Mark, 50 %of cross sectional area - 20% NORMAL0 ft. MGO - General Observation - MH CONN 3:00 ACTIVE0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:40AM2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COAT 70% START 9:00 TO 3:002.7 ft. MGO - General Observation - 63" RCP94.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE415.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE738.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE1010.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING CONCRETE1010.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish1010.1 ft. MGO - General Observation - MAG COAT 70% FINISH1010.6 ft. AMH - Downstream Manhole, Survey Ends - 5:30AM

Observation photos (6)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - 63" RCP

    2.7 ft. - General Observation - 63" RCP

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    94.5 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    415.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    738.8 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

Observations (15)

DistanceCodeObservation
0MWM20% NORMAL
0MGOMH CONN 3:00 ACTIVE
0MWL
0AMH4:40AM
2.7MGO63" RCP
2SSSBLISTERING CONCRETE
2DAGS
1010.1SSSBLISTERING CONCRETE
1010.1DAGS
2MGOMAG COAT 70% START 9:00 TO 3:00
415.2SSSBLISTERING CONCRETE
1010.6AMH5:30AM
94.5SSSBLISTERING CONCRETE
738.8SSSBLISTERING CONCRETE
1010.1MGOMAG COAT 70% FINISH

Properties (4)

custom_field_three
BLISTERING CONCRETE
custom_field_two
4
customer
LACSD
datetime
2018-03-13T02:42:48-07:00