- Date
- 03/13/2018
- W/O
- 0694533
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00176
- PipeID
- P10801
- Time
- 2:41 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G6968
- Sewer Name
- H JOINT OUTFALL H - UNIT 4 RELIEF
- City
- PICO RIVERA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 19A
- Purpose
- Routine Assessment
- Project
- 20180313MDM_JOINT_OUTFALL_H_UNIT_4_RELIEF
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 63 in.
- Upstream MH
- H 0352
- Downstream MH
- H 0351
- Dir. of Survey
- Downstream
- Length Surveyed
- 298.7 ft.
- Total Length
- 298.7 ft.
- Structural Index
- 2
- Structural Quick
- 2K00
- Structural Rating
- 120
- O&M Index
- 2
- O&M Quick
- 412K
- O&M Rating
- 120
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 240
Pipe schematic from manhole H 0352 to H 0351 Observation photos (5)

0 ft. - Water Mark, 50 %of cross sectional area - NORMAL 20%

2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING CONCRETE

2 ft. - General Observation - MAG COAT 70% START 9:00 TO 3:00

8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

122.9 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE