Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 10, 2018, 08:48 AM
  • C 0313A_C 0313_3102018_031948.mp4

Date
03/10/2018
W/O
0693749
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00135
PipeID
P09776
Time
12:48 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0773
Sewer Name
C JOINT OUTFALL C - UNIT 6F
City
CERRITOS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20180310MDM_JOINT_OUTFALL_C_UNIT_6F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
15 in.
Upstream MH
C 0313A
Downstream MH
C 0313
Dir. of Survey
Downstream
Length Surveyed
365.8 ft.
Total Length
365.8 ft.
Structural Index
5
Structural Quick
5C32
Structural Rating
113
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
5
Overall Quick
Overall Rating
115
Pipe schematic from manhole C 0313A to C 0313
MH: C 0313AMH: C 0313downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: NO - INMSIDE MH0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:20AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG12 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG13 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM17.6 ft. SRC - Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR19 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM21.4 ft. SRC - Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM23.2 ft. SRV - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: YES - LONG30 ft. SRV - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM36.4 ft. SRV - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM45.2 ft. SRC - Surface Reinforcement Corroded, at 03 o'clock, within 8 inches of joint: YES - LONG46.3 ft. SRC - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM48.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 10 o'clock, within 8 inches of joint: NO - CIRCUM53.5 ft. SRC - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM55.7 ft. SRC - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR61.1 ft. SRC - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM97.5 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - LOMG119 ft. SRC - Surface Reinforcement Corroded, from 09 to 11 o'clock, within 8 inches of joint: NO - CIRCUM129.9 ft. SRC - Surface Reinforcement Corroded, from 10 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR136.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 04 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR167 ft. SRC - Surface Reinforcement Corroded, at 02 o'clock, within 8 inches of joint: NO - LONG181.9 ft. SRC - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO - CIRCUM185.2 ft. SRC - Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM187.1 ft. SRC - Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: NO - CIRCUM188.6 ft. SRC - Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: YES, Finish - CIRCUM230.9 ft. SRV - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO - CIRCUM259.9 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - LONG295.2 ft. SRV - Surface Reinforcement Visible, at 03 o'clock, within 8 inches of joint: YES - LONG299.8 ft. SRC - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM303.9 ft. SRC - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM315.4 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM321.5 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM348.1 ft. SRC - Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM351.3 ft. SRC - Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: YES, Finish - CIRCUM365.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG365.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE365.8 ft. AMH - Downstream Manhole, Survey Ends - 4:10AM

Observation photos (15)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    12 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM

    13 ft. - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM

  • Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    17.6 ft. - Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    30 ft. - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    55.7 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    129.9 ft. - Surface Reinforcement Corroded, from 10 to 04 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, at 02 o'clock, within 8 inches of joint: NO - LONG

    167 ft. - Surface Reinforcement Corroded, at 02 o'clock, within 8 inches of joint: NO - LONG

  • Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO - CIRCUM

    181.9 ft. - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    185.2 ft. - Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: NO - CIRCUM

    187.1 ft. - Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM

    299.8 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM

  • Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM

    315.4 ft. - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM

  • Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    348.1 ft. - Surface Reinforcement Corroded, from 02 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM

Observations (42)

DistanceCodeObservation
46.3SRCCIRCUM
2SSSBLISTERING PEELING CONCRETE
230.9SRVCIRCUM
365.4SAPSEVERE AGG
188.6SRCCIRCUM
13SRVLONG CIRCUM
36.4SRVCIRCUM
48.4SRCCIRCUM
181.9SRCCIRCUM
19SRVLONG CIRCUM
45.2SRCLONG
167SRCLONG
0MWM
315.4SRVLONG CIRCUM
55.7SRCLONG CIRCUM REBAR
365.4SSSBLISTERING PEELING CONCRETE
0DAGSINMSIDE MH
30SRVCIRCUM
321.5SRVLONG CIRCUM
23.2SRVLONG
0MWL
303.9SRCLONG CIRCUM
17.6SRCLONG CIRCUM REBAR
129.9SRCLONG CIRCUM REBAR
259.9SRVLONG
97.5SRVLOMG
21.4SRCLONG CIRCUM
185.2SRCCIRCUM
119SRCCIRCUM
348.1SRCCIRCUM
187.1SRCCIRCUM
2SAPSEVERE AGG
299.8SRCLONG CIRCUM
61.1SRCLONG CIRCUM
351.3SRCCIRCUM
0AMH3:20AM
136.3SRCLONG CIRCUM REBAR
12SAPSEVERE AGG
53.5SRCCIRCUM
295.2SRVLONG
0MGOConn. @ Mh, 9 O' Clock. Active
365.8AMH4:10AM

Properties (4)

custom_field_three
CORRODED LONG CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2018-03-10T00:48:14-08:00