- Date
- 11/07/2017
- W/O
- 668788
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00462
- PipeID
- P20885
- Time
- 3:38 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K5212
- Sewer Name
- 05 INGLEWOOD TRUNK #1 RELIEF
- City
- INGLEWOOD
- Loc. details
- Other
- Location Code
- Z
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 05
- Purpose
- Routine Assessment
- Project
- WO_668788_TV05326_NOV2017
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Width
- 15 in.
- Upstream MH
- 05 2489
- Downstream MH
- 05 0524
- Dir. of Survey
- Upstream
- Length Surveyed
- 379.7 ft.
- Total Length
- 379.7 ft.
- Structural Index
- 3
- Structural Quick
- 3100
- Structural Rating
- 3
- O&M Index
- 2
- O&M Quick
- 2N00
- O&M Rating
- 150
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 153
Pipe schematic from manhole 05 2489 to 05 0524 Observation photos (2)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

61.7 ft. - Fracture Spiral, from 03 to 06 o'clock, within 8 inches of joint: YES