Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 6, 2018, 11:20 AM
  • 01 1126_01 1125_06022018_033756.mp4

Date
02/06/2018
W/O
685073
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00210
PipeID
P01978
Time
3:20 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5432
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
WO_685073_TV01246_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1126
Downstream MH
01 1125
Dir. of Survey
Downstream
Length Surveyed
281.3 ft.
Total Length
281.3 ft.
Structural Index
3
Structural Quick
513I
Structural Rating
159
O&M Index
2
O&M Quick
3111
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
163
Pipe schematic from manhole 01 1126 to 01 1125
MH: 01 1126MH: 01 1125downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 11260 ft. MWL - Water Level, 5 %of cross sectional area4.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES11.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES21.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"27.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start62.6 ft. RML - Roots Medium Lateral, at 02 o'clock, 40 %, within 8 inches of joint: NO62.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"67.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"106.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"114.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"144.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"144.6 ft. HVV - Hole Void Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - SOIL SHOWING - AT CONNECTION150.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"176.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"197.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"220.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"220.6 ft. RFL - Roots Fine Lateral, at 10 o'clock242.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"247.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"279.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish281.3 ft. AMH - Downstream Manhole, Survey Ends - 01 1125

Observation photos (4)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    4.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    11.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    27.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Hole Void Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - SOIL SHOWING - AT CONNECTION

    144.6 ft. - Hole Void Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - SOIL SHOWING - AT CONNECTION

Observations (23)

DistanceCodeObservation
0MWM
114.3TF
279.6CM
281.3AMH01 1125
67.6TF
150.3TF
197.4TF
144.6HVVAT CONNECTION
220.6TF
11.9CL
62.6RML
106.8TF
4.6CL
21.1TF
247.8TF
220.6RFL
0AMH01 1126
176.3TF
27.6CM
0MWL
242.9TF
62.6TF
144.5TB

Properties (4)

additional_info
SC347070
custom_field_two
1
customer
LACSD
datetime
2018-02-06T03:20:57-08:00