- Date
- 02/06/2018
- W/O
- 685073
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00210
- PipeID
- P01978
- Time
- 3:20 AM
- Certificate
- U-508-7069
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K5432
- Sewer Name
- 01 HUNTINGTON PARK TRUNK
- City
- HUNTINGTON PARK
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 04
- Purpose
- Routine Assessment
- Project
- WO_685073_TV01246_FEB2018
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Width
- 15 in.
- Upstream MH
- 01 1126
- Downstream MH
- 01 1125
- Dir. of Survey
- Downstream
- Length Surveyed
- 281.3 ft.
- Total Length
- 281.3 ft.
- Structural Index
- 3
- Structural Quick
- 513I
- Structural Rating
- 159
- O&M Index
- 2
- O&M Quick
- 3111
- O&M Rating
- 4
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 163
Pipe schematic from manhole 01 1126 to 01 1125 Observation photos (4)

4.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

11.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

27.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

144.6 ft. - Hole Void Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - SOIL SHOWING - AT CONNECTION