Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 5, 2018, 10:34 AM
  • 05 0723_05 0722_05022018_024626.mp4

Date
02/05/2018
W/O
685334
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00521
PipeID
P05946
Time
2:34 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5398
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #1
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
WO_685334_TV05333_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0723
Downstream MH
05 0722
Dir. of Survey
Downstream
Length Surveyed
307.2 ft.
Total Length
307.2 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 05 0723 to 05 0722
MH: 05 0723MH: 05 0722downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 07230 ft. MWM - Water Mark, 35 %of cross sectional area6.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start44.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"92.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"143 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6" - FRACTURES190.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"244.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"291.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"305 ft. MGO - General Observation - ENCRUSTATION THROUGHOUT THE REACH, FROM 08 TO 04 O'CLOCK305.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish307.2 ft. AMH - Downstream Manhole, Survey Ends - 05 0722

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    6.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
305.6CM
307.2AMH05 0722
190.9TFA
0MWL
0AMH05 0723
305MGOENCRUSTATION THROUGHOUT THE REACH, FROM 08 TO 04 O'CLOCK
0MWM
244.4TFA
291.7TFA
143TFDFRACTURES
92.4TF
44.4TF
6.5CM

Properties (4)

additional_info
SC346977
custom_field_two
2
customer
LACSD
datetime
2018-02-05T02:34:17-08:00