Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 7, 2018, 10:20 AM
  • 04 0080_04 0079 _07022018_023959.mp4

Date
02/07/2018
W/O
685064
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00415
PipeID
P11818
Time
2:20 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5433
Sewer Name
04 SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
01
Purpose
Routine Assessment
Project
WO_685064_TV04009_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
04 0079
Downstream MH
04 0080
Dir. of Survey
Upstream
Length Surveyed
353 ft.
Total Length
353 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
210
O&M Index
2
O&M Quick
4132
O&M Rating
154
Overall Index
2
Overall Quick
Overall Rating
364
Pipe schematic from manhole 04 0079 to 04 0080
MH: 04 0079MH: 04 0080upstream0 ft. AMH - Upstream Manhole, Survey Ends - 04 00800.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish0.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish32 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"34.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"73.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"110.1 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES111.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"121.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"154.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"173.7 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6" - GAP AT BEGINNING OF LATERAL PIPE209.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"212.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"253.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"260.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"265.1 ft. ID - Infiltration Dripper, at 01 o'clock, within 8 inches of joint: YES296.5 ft. RFC - Roots Fine Connection, from 02 to 04 o'clock296.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"296.5 ft. RBL - Roots Ball Lateral, at 02 o'clock, 75 %298 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"299.1 ft. RFC - Roots Fine Connection, from 08 to 10 o'clock343.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start345.3 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6" - GAP AT LATERAL WITH POSSIBLE SOIL COMING IN346.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"350 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start353 ft. AMH - Downstream Manhole, Survey Begins - 04 0079353 ft. MWM - Water Mark, 15 %of cross sectional area353 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES, Start

    9.2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start

  • Infiltration Dripper, at 01 o'clock, within 8 inches of joint: YES

    87.9 ft. - Infiltration Dripper, at 01 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

    242.9 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

Observations (29)

DistanceCodeObservation
353AMH04 0080
0AMH04 0079
198.4TF
92.1TF
7.7TFDGAP AT LATERAL WITH POSSIBLE SOIL COMING IN
56.5RFC
6.2TF
3CM
277.5TF
9.2DAE
352.2DAE
318.4TF
56.5TF
55TF
0MWM
179.3TFDGAP AT BEGINNING OF LATERAL PIPE
140.8TF
242.9ID
99.8TF
0MWL
143.4TF
53.9RFC
87.9ID
241.6TF
352.2CM
56.5RBL
321TF
231.8TFA
279.8TF

Properties (4)

additional_info
SC347071
custom_field_two
3
customer
LACSD
datetime
2018-02-07T02:20:29-08:00