Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 7, 2018, 10:00 AM
  • 04 0079_04 0078A _07022018_021945.mp4

Date
02/07/2018
W/O
685064
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00415
PipeID
P11817
Time
2:00 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5433
Sewer Name
04 SHERMAN TRUNK
City
WEST HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
01
Purpose
Routine Assessment
Project
WO_685064_TV04009_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
04 0078A
Downstream MH
04 0079
Dir. of Survey
Upstream
Length Surveyed
320.6 ft.
Total Length
320.7 ft.
Structural Index
3
Structural Quick
5142
Structural Rating
94
O&M Index
2
O&M Quick
4334
O&M Rating
32
Overall Index
3
Overall Quick
Overall Rating
126
Pipe schematic from manhole 04 0078A to 04 0079
MH: 04 0078AMH: 04 0079upstream0 ft. AMH - Upstream Manhole, Survey Ends - 04 00794.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish4.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish36.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"36.5 ft. RBL - Roots Ball Lateral, at 02 o'clock, 90 %36.7 ft. IS - Infiltration Stain, at 10 o'clock, within 8 inches of joint: YES38.2 ft. RMC - Roots Medium Connection, from 03 to 05 o'clock, 10 %, within 8 inches of joint: NO39.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"81.5 ft. RML - Roots Medium Lateral, at 10 o'clock, 10 %, within 8 inches of joint: NO81.5 ft. RFC - Roots Fine Connection, from 07 to 09 o'clock81.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"85.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"85.6 ft. RBL - Roots Ball Lateral, at 02 o'clock, 95 %124.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"124.2 ft. RML - Roots Medium Lateral, at 10 o'clock, 15 %, within 8 inches of joint: NO135.4 ft. RMC - Roots Medium Connection, from 02 to 05 o'clock, 30 %, within 8 inches of joint: NO135.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"135.4 ft. RBL - Roots Ball Lateral, at 02 o'clock, 90 %137.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"174.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start174.7 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish176.5 ft. RFC - Roots Fine Connection, at 10 o'clock176.6 ft. RFL - Roots Fine Lateral, at 10 o'clock176.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - DAMAGED182.6 ft. RFJ - Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YES183.5 ft. HSV - Hole Soil Visible, from 03 to 04 o'clock, within 8 inches of joint: YES183.7 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start183.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish193.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"214.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"222.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"257.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"270.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"311.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start311.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start316.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"318.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"320.7 ft. MWL - Water Level, 5 %of cross sectional area320.7 ft. AMH - Downstream Manhole, Survey Begins - 04 0078A320.7 ft. MWM - Water Mark, 15 %of cross sectional area

Observation photos (7)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    9.5 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    137 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Hole Soil Visible, from 03 to 04 o'clock, within 8 inches of joint: YES

    137.2 ft. - Hole Soil Visible, from 03 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YES

    138.1 ft. - Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    146.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Connection, from 02 to 05 o'clock, 30 %, within 8 inches of joint: NO

    185.3 ft. - Roots Medium Connection, from 02 to 05 o'clock, 30 %, within 8 inches of joint: NO

Observations (40)

DistanceCodeObservation
0MWL
320.7AMH04 0079
235.1TF
9.5CM
63.2TF
316DAE
9.5DAE
316.2CM
146FM
137FM
185.3RMC
50TFC
144.1RFL
282.5RMC
196.5TF
239.2RML
146.1CM
239.2RFC
284IS
185.3TF
239.1TF
144.2RFC
235.1RBL
127.4TF
105.9TF
4.1TFC
137.2HSV
284.2TF
98TF
138.1RFJ
284.2RBL
0AMH04 0078A
196.5RML
281.6TF
182.8TF
137CM
144TFDAMAGED
0MWM
2.1TF
185.3RBL

Properties (4)

additional_info
SC347071
custom_field_two
1
customer
LACSD
datetime
2018-02-07T02:00:57-08:00