Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 6, 2018, 08:47 AM
  • 01 0794_01 0793_06022018_010442.mp4

Date
02/06/2018
W/O
684850
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00197
PipeID
P01496
Time
12:47 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5431
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
WO_684850_TV01264_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0794
Downstream MH
01 0793
Dir. of Survey
Downstream
Length Surveyed
293.2 ft.
Total Length
293.2 ft.
Structural Index
4
Structural Quick
4K31
Structural Rating
235
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
235
Pipe schematic from manhole 01 0794 to 01 0793
MH: 01 0794MH: 01 0793downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 07942.8 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start12.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"89 ft. H - Hole, at 11 o'clock, within 8 inches of joint: YES112.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"133.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"163.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"181.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"214.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"232.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"266.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"281.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"292 ft. MGO - General Observation - SOIL VISIBLE INSIDE THE FRACTURES THROUGHOUT THE REACH293.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK293.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0793293.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
0MGOCONNECTION AT MH 3 O'CLOCK
293.2MGOCONNECTION AT MH 9 O'CLOCK
163.4TFC
133.2TFC
2.8FM
89H
214.8TFC
0MWM
293.2AMH01 0793
0MWL
12.4TFC
292MGOSOIL VISIBLE INSIDE THE FRACTURES THROUGHOUT THE REACH
64.2TFC
0AMH01 0794
281.1TFC
181.2TFC
112.4TFC
266.3TFC
293.2FM
75.9TFC
232.8TFC

Properties (4)

additional_info
SC347069
custom_field_two
1
customer
LACSD
datetime
2018-02-06T00:47:27-08:00