Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 6, 2018, 07:05 AM
  • 01 0798A_01 0798_05022018_232207.mp4

Date
02/05/2018
W/O
684850
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00197
PipeID
P01501
Time
11:05 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5431
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
WO_684850_TV01264_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0798A
Downstream MH
01 0798
Dir. of Survey
Downstream
Length Surveyed
290.8 ft.
Total Length
290.8 ft.
Structural Index
4
Structural Quick
4200
Structural Rating
8
O&M Index
2
O&M Quick
4112
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
14
Pipe schematic from manhole 01 0798A to 01 0798
MH: 01 0798AMH: 01 0798downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 0798A0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start14.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"23.6 ft. RFJ - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YES37.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"40.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"61.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"79.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"87.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"111.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"126.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"133 ft. MGO - General Observation - DAMAGED SURFACE @ 11 O'CLOCK138.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"162 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"171.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"192 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"205.2 ft. RFJ - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES220 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"243.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"264.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"286.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish290.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0798290.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK290.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (1)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (27)

DistanceCodeObservation
61.3TFC
14.1TFC
286.5FM
290.8AMH01 0798
79.4TFC
133MGODAMAGED SURFACE @ 11 O'CLOCK
171.2TFC
290.8MGOCONNECTION AT MH 3 O'CLOCK
37.6TFC
111.7TFC
205.2RFJ
162TFC
0MWM
2.4FM
0AMH01 0798A
126.9TFC
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK
264.8TFC
87.8TFC
290.8MGOCONNECTION AT MH 9 O'CLOCK
138.7TFC
243.7TFC
220TFC
40.4TFC
23.6RFJ
192TFC

Properties (4)

additional_info
SC347069
custom_field_two
1
customer
LACSD
datetime
2018-02-05T23:05:44-08:00