Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 6, 2018, 08:21 AM
  • 01 1369_01 0795_06022018_003125.mp4

Date
02/06/2018
W/O
684850
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00197
PipeID
P01498
Time
12:21 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5431
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
WO_684850_TV01264_FEB2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1369
Downstream MH
01 0795
Dir. of Survey
Downstream
Length Surveyed
134.1 ft.
Total Length
134.1 ft.
Structural Index
4
Structural Quick
514D
Structural Rating
111
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
115
Pipe schematic from manhole 01 1369 to 01 0795
MH: 01 1369MH: 01 0795downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 13693.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"7.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start7.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish12 ft. HSV - Hole Soil Visible, at 11 o'clock, within 8 inches of joint: YES55.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"79.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"106.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"127.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"131.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish134.1 ft. AMH - Downstream Manhole, Survey Ends - 01 0795

Observation photos (2)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    3.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7.5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
127.9TFC
7.5FM
106.6TFC
134.1AMH01 0795
7.5FL
3.4FL
12HSV
79.5TFC
0MWM
7TFC
131.6FM
0MWL
55.3TF
0AMH01 1369

Properties (4)

additional_info
SC347069
custom_field_two
1
customer
LACSD
datetime
2018-02-06T00:21:51-08:00