- Date
- 02/26/2018
- W/O
- 0685105
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00561
- PipeID
- P21471
- Time
- 12:55 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H0753
- Sewer Name
- 08 MAIN STREET P.P. INFLUENT SEWER
- City
- CARSON
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 08
- Page No.
- 10
- Purpose
- Routine Assessment
- Project
- 20180226MDM_MAIN_STREET_P_P_INFLUENT_SEWER
- Material
- CIP
- Shape
- Circular
- Height
- 30 in.
- Upstream MH
- 08 0001
- Downstream MH
- 08 0000
- Dir. of Survey
- Downstream
- Length Surveyed
- 15.7 ft.
- Total Length
- 15.7 ft.
- Structural Index
- 4
- Structural Quick
- 5141
- Structural Rating
- 18
- O&M Index
- 5
- O&M Quick
- 5100
- O&M Rating
- 5
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 23
Pipe schematic from manhole 08 0001 to 08 0000 Observation photos (5)

2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - LONG CIRCUM REBAR

2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

7 ft. - Surface Corrosion Metal Pipe, from 10 to 02 o'clock, within 8 inches of joint: YES - 30% MISSING PIPE

7 ft. - Surface Corrosion Metal Pipe, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - 30% MISSING PIPE

12.1 ft. - Surface Corrosion Metal Pipe, from 10 to 02 o'clock, within 8 inches of joint: YES - 30% MISSING