Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 5, 2018, 06:25 AM
  • 05 0660_05 0659 _04012018_224921.mp4

Date
01/04/2018
W/O
679249
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00520
PipeID
P05885
Time
10:25 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5307
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
10
Purpose
Routine Assessment
Project
WO_679249_TV05103_JAN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 0660
Downstream MH
05 0659
Dir. of Survey
Downstream
Length Surveyed
310.8 ft.
Total Length
310.8 ft.
Structural Index
2
Structural Quick
5132
Structural Rating
24
O&M Index
2
O&M Quick
3123
O&M Rating
10
Overall Index
2
Overall Quick
Overall Rating
34
Pipe schematic from manhole 05 0660 to 05 0659
MH: 05 0660MH: 05 0659downstream0 ft. VC - Vermin Cockroach0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 06603.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start14.2 ft. CC - Crack Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES15.4 ft. OBZ - Obstacles Other, 10 %of cross sectional area, from 04 to 08 o'clock - NOT VISIBLE19.7 ft. CC - Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES34.3 ft. OBZ - Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock - NOT VISIBLE40 ft. CC - Crack Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES42.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"71.8 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES91.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"122.8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES140 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"170.3 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES170.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES194 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"231.7 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES239 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"273.7 ft. FC - Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES280.9 ft. HSV - Hole Soil Visible, at 10 o'clock, within 8 inches of joint: YES306.4 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES310.8 ft. AMH - Downstream Manhole, Survey Ends - 05 0659310.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE310.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (11)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES

    14.2 ft. - Crack Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES

    19.7 ft. - Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    71.8 ft. - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES

    122.8 ft. - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    170.3 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

    170.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    231.7 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES

    273.7 ft. - Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES

  • Hole Soil Visible, at 10 o'clock, within 8 inches of joint: YES

    280.9 ft. - Hole Soil Visible, at 10 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    306.4 ft. - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
310.8AMH05 0659
140TFA
42.6TFA
122.8FC
15.4OBZNOT VISIBLE
40CC
0VC
71.8CM
310.8MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
170.3CL
0MWL
14.2CC
310.8DAGS
0MWM
273.7FC
19.7CC
0AMH05 0660
91.9TFA
239TFC
194TFA
170.3SSS
34.3OBZNOT VISIBLE
231.7CL
3.6DAGS
306.4FL
280.9HSV

Properties (4)

additional_info
SC346901
custom_field_two
1
customer
LACSD
datetime
2018-01-04T22:25:29-08:00