- Date
- 01/05/2018
- W/O
- 679249
- Weather
- Dry
- Operator/Surveyor
- R.VARGAS
- Sewer ID
- Z00520
- PipeID
- P05875
- Time
- 4:01 AM
- Certificate
- U-209-211
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K5307
- Sewer Name
- 05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK
- City
- INGLEWOOD
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 10
- Purpose
- Routine Assessment
- Project
- WO_679249_TV05103_JAN2018
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 21 in.
- Width
- 21 in.
- Upstream MH
- 05 0650
- Downstream MH
- 05 0649
- Dir. of Survey
- Downstream
- Length Surveyed
- 291.5 ft.
- Total Length
- 291.5 ft.
- Structural Index
- 3
- Structural Quick
- 3221
- Structural Rating
- 8
- O&M Index
- 2
- O&M Quick
- 3121
- O&M Rating
- 6
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 14
Pipe schematic from manhole 05 0650 to 05 0649 Observation photos (4)

2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

25.8 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

159.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

252.1 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start