Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 5, 2018, 11:37 AM
  • 05 0651_05 0650 _05012018_040138.mp4

Date
01/05/2018
W/O
679249
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00520
PipeID
P05876
Time
3:37 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5307
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
10
Purpose
Routine Assessment
Project
WO_679249_TV05103_JAN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
05 0651
Downstream MH
05 0650
Dir. of Survey
Downstream
Length Surveyed
352.9 ft.
Total Length
352.9 ft.
Structural Index
3
Structural Quick
4132
Structural Rating
15
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
20
Pipe schematic from manhole 05 0651 to 05 0650
MH: 05 0651MH: 05 0650downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 05 06510 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start76.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"119.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"170.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"216.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"218.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish218.8 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start241 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish261.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"287.4 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES292.8 ft. CM - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES309.7 ft. OBZ - Obstacles Other, 10 %of cross sectional area, from 04 to 08 o'clock - NOT VISIBLE312.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"327.6 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES, Start336.7 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES, Finish347.5 ft. CC - Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES352.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE352.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish352.9 ft. VC - Vermin Cockroach352.9 ft. AMH - Downstream Manhole, Survey Ends - 05 0650352.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK ACTIVE

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    218.8 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    287.4 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

    292.8 ft. - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES, Start

    327.6 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

    347.5 ft. - Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

Observations (27)

DistanceCodeObservation
261.1TFC
218.8CM
0MGOCONNECTION AT MH 9 O'CLOCK ACTIVE
347.5CC
170.4TFC
352.9MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
352.9DAGS
312.7TFC
0AMH05 0651
119.1TFC
287.4CL
76.5TFC
309.7OBZNOT VISIBLE
0MWM
352.9VC
352.9AMH05 0650
241FM
327.6CL
336.7CL
2.1DAGS
0MWL
216.6TFC
352.9MGOCONNECTION AT MH 9 O'CLOCK ACTIVE
218.8FM
0MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
292.8CM
3.1CM

Properties (4)

additional_info
SC346901
custom_field_two
3
customer
LACSD
datetime
2018-01-05T03:37:34-08:00