Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 5, 2018, 07:53 AM
  • 05 0658_05 0657 _05012018_001116.mp4

Date
01/04/2018
W/O
679249
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00520
PipeID
P05883
Time
11:53 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5307
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
10
Purpose
Routine Assessment
Project
WO_679249_TV05103_JAN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 0658
Downstream MH
05 0657
Dir. of Survey
Downstream
Length Surveyed
349.2 ft.
Total Length
349.2 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 05 0658 to 05 0657
MH: 05 0658MH: 05 0657downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 06580 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start53.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES66.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"113.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"158.4 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES165 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"216.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"264.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"315.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"349.2 ft. AMH - Downstream Manhole, Survey Ends - 05 0657349.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED349.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish349.2 ft. VC - Vermin Cockroach349.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    53.1 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    158.4 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
2DAGS
0AMH05 0658
165TFA
0MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
113.4TFA
349.2AMH05 0657
264.8TFA
349.2MGOCONNECTION AT MH 9 O'CLOCK CAPPED
53.1CL
349.2DAGS
349.2VC
216.5TFA
349.2MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
0MWL
315.7TFA
0MGOCONNECTION AT MH 9 O'CLOCK CAPPED
0MWM
158.4CL
66.3TFA

Properties (4)

additional_info
SC346901
custom_field_two
3
customer
LACSD
datetime
2018-01-04T23:53:09-08:00