Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 5, 2018, 06:52 AM
  • 05 0659_05 0658 _04012018_232516.mp4

Date
01/04/2018
W/O
679249
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00520
PipeID
P05884
Time
10:52 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5307
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
10
Purpose
Routine Assessment
Project
WO_679249_TV05103_JAN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 0659
Downstream MH
05 0658
Dir. of Survey
Downstream
Length Surveyed
353.7 ft.
Total Length
353.7 ft.
Structural Index
2
Structural Quick
2600
Structural Rating
12
O&M Index
2
O&M Quick
2212
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
18
Pipe schematic from manhole 05 0659 to 05 0658
MH: 05 0659MH: 05 0658downstream0 ft. VC - Vermin Cockroach0 ft. AMH - Upstream Manhole, Survey Begins - 05 06590 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE3.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start76.4 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES80.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"99.6 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES141.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"184.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"234 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES239.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"246.2 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES276 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES279.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"305 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES353.7 ft. VC - Vermin Cockroach353.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish353.7 ft. AMH - Downstream Manhole, Survey Ends - 05 0658353.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED353.7 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    76.4 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    99.6 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    246.2 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
276CL
99.6CL
141.3TFA
0VC
184.2TFA
234CL
76.4CL
353.7VC
239.4TFC
0AMH05 0659
246.2CL
279.5TFA
353.7DAGS
353.7AMH05 0658
0MWM
305CL
0MWL
0MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
353.7MGOCONNECTION AT MH 9 O'CLOCK CAPPED
353.7MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
80.4TFA
3.5DAGS

Properties (4)

additional_info
SC346901
custom_field_two
3
customer
LACSD
datetime
2018-01-04T22:52:16-08:00