Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 4, 2018, 09:41 AM
  • 05 0669_05 0668 _04012018_015944.mp4

Date
01/04/2018
W/O
679249
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00520
PipeID
P05896
Time
1:41 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5306
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
10
Purpose
Routine Assessment
Project
WO_679249_TV05103_JAN2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 0669
Downstream MH
05 0668
Dir. of Survey
Downstream
Length Surveyed
373.4 ft.
Total Length
373.4 ft.
Structural Index
2
Structural Quick
3124
Structural Rating
13
O&M Index
2
O&M Quick
3321
O&M Rating
13
Overall Index
2
Overall Quick
Overall Rating
26
Pipe schematic from manhole 05 0669 to 05 0668
MH: 05 0669MH: 05 0668downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 05 06690 ft. VC - Vermin Cockroach0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK ACTIVE1.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start31.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES61.1 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES80.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"91.2 ft. CC - Crack Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES103.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES128.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"154.9 ft. CC - Crack Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES181 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"181 ft. RML - Roots Medium Lateral, at 12 o'clock, 20 %, within 8 inches of joint: YES191.4 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES193.8 ft. RML - Roots Medium Lateral, at 10 o'clock, 10 %, within 8 inches of joint: YES193.8 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"211.5 ft. RML - Roots Medium Lateral, at 12 o'clock, 10 %, within 8 inches of joint: YES211.5 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 4"232.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 4"271 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES283.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"335.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"373.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish373.4 ft. VC - Vermin Cockroach373.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK ACTIVE373.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE373.4 ft. AMH - Downstream Manhole, Survey Ends - 05 0668

Observation photos (11)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    1.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    31.1 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    61.1 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES

    91.2 ft. - Crack Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    103.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES

    154.9 ft. - Crack Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Roots Medium Lateral, at 12 o'clock, 20 %, within 8 inches of joint: YES

    181 ft. - Roots Medium Lateral, at 12 o'clock, 20 %, within 8 inches of joint: YES

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    191.4 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Roots Medium Lateral, at 10 o'clock, 10 %, within 8 inches of joint: YES

    193.8 ft. - Roots Medium Lateral, at 10 o'clock, 10 %, within 8 inches of joint: YES

  • Roots Medium Lateral, at 12 o'clock, 10 %, within 8 inches of joint: YES

    211.5 ft. - Roots Medium Lateral, at 12 o'clock, 10 %, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    271 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

Observations (30)

DistanceCodeObservation
193.8RML
211.5RML
0MWM
1.6DAGS
373.4DAGS
232.2TFC
31.1CL
191.4FL
154.9CC
80.3TFA
61.1CL
181TFA
271CL
373.4VC
128.8TFA
373.4MGOCONNECTION AT MH 9 O'CLOCK ACTIVE
103.1CL
0MWL
373.4MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
0MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
335.8TFC
373.4AMH05 0668
283.8TFA
0AMH05 0669
91.2CC
181RML
193.8TBA
0VC
0MGOCONNECTION AT MH 9 O'CLOCK ACTIVE
211.5TBA

Properties (4)

additional_info
SC346475
custom_field_two
4
customer
LACSD
datetime
2018-01-04T01:41:21-08:00